BAM High Voltage Power Capacitor
Maombi na Viwango:
Capacitor ya volteji ya juu hutumiwa zaidi katika mfumo wa AC Power na 50Hz ili kuboresha kipengele cha nguvu. Utendaji unalingana na GB 3083.2-89 《Kipima cha shunt cha juu cha voltage》na IEC 60871-1987.
GB/T11024-2010 Kiwango cha Kitaifa 《Volaiti iliyokadiriwa 1kV au zaidi ya vipitishio vya shunt kwa mifumo ya nguvu ya AC
JB/7112-2000 Kiwango cha Sekta ya Mashine 《Kipima Kilichounganishwa cha HV Shunt
DL/T628-1997 Kiwango cha Sekta ya Nishati ya Umeme 《Kipima Kilichounganishwa cha HV Shunt Kuagiza Mahitaji ya Kiufundi
Masharti ya Matumizi:
1.Muinuko: chini ya 1000m; Halijoto ya Mazingira: -40 ℃ ~ +40 ℃.
2.Hakuna mtetemo mkali wa mitambo, hakuna gesi na mvuke hatari, hakuna umeme, na vilipuzi, na vumbi linalolipuka mahali hapo.
3.Votesheni inayoendelea ya voltage: 1.00 Un, max ya muda mrefu, Over voltage: less.1 Un.
4.Imetulia kupita kiasi (ikiwa ni pamoja na hali ya sasa) chini ya 1.3 In.
5.Na voltage ya kusimama: kati ya terminal 2.15, voltage iliyokadiriwa wakati kwa sekunde 10, kati ya vituo na kontena 42kV kwa sekunde 10.
Tabia kuu za kiufundi:
1.Iliyopimwa voltage: 6.3kV, 6.6kV, 6.6/√3kV, 7.96kV, 10.5kV, 11kV, 11kV, 11/√3kV, tafadhali iliyoonyeshwa kwa mpangilio ikiwa unataka uwezo mwingine maalum.
2.Iliyopewa uwezo: 33~334kvar tafadhali imeonyeshwa kwa mpangilio ikiwa unataka uwezo mwingine maalum.
3.Uvumilivu wa uwezo: -5 ~ 15%.
4.Malaika wa kupoteza thamani ya tangential: filamu & papaer kati tg θ≦0.08%,filamu ya kati tg θ≦0.05%.
5.Kuhimili voltage: inaweza kumudu voltage iliyokadiriwa mara AC2.15 au DC4.3 kati ya rangi ya uwezo, hudumu kama sekunde 10 bila kukatika au flash, BIL: 6kV(30kV), 10kV(42Kv).
6.Kutokwa kwa bure: ina upinzani wa ndani, dakika 10 baada ya kukata usambazaji wa umeme, voltage iliyobaki itapungua hadi 75V kutoka √2 Un.
7.Upeo. Ya sasa: inaendesha vizuri chini ya voltage iliyokadiriwa wakati 1.3, juu ya voltage, uwezo wa kustahimili na mawimbi ya harmonic ambayo hayawezi kuzidi dakika 1 kila masaa 24.
8.Max.Current: kukimbia vizuri chini ya 1.3 wakati lilipimwa voltage voltage, juu ya voltage, uwezo wa kuvumiliana chanya na harmonic wimbi ambayo haiwezi 1.43 wakati lilipimwa sasa.
9.Standard: GB/T 112024.1-2001, IEC6087:1997.
Sehemu tofauti ya Capacitor ya Nguvu
Mfano wa BAM | Kiwango cha Voltage (kV) | Pato Lililokadiriwa (kVAr) | Ukadiriaji wa Uwezo(uF) | Iliyokadiriwa Sasa Katika(A) |
10.5-50-1W | 10.5 | 50 | 1.444 | 4.762 |
6.35-30-1W | 6.35 | 30 | 2.368 | 4.724 |
6.35-50-1W | 6.35 | 50 | 3.946 | 7.873 |
6.3-30-1W | 6.3 | 30 | 2.4 | 4.76 |
6.3-50-1W | 6.3 | 50 | 4 | 7.9 |
6.3-100-1W | 6.3 | 100 | 8 | 15.9 |
6.3-200-1W | 6.3 | 200 | 16 | 31.7 |
6.3-300-1W | 6.3 | 300 | ishirini na nne | 47.6 |
6.3-334-1W | 6.3 | 334 | 26.8 | 53 |
10.5-50-1W | 10.5 | 50 | 1.44 | 4.8 |
10.5-100-1W | 10.5 | 100 | 2.9 | 9.5 |
10.5-150-1W | 10.5 | 150 | 4.3 | 14.3 |
10.5-200-1W | 10.5 | 200 | 5.8 | 19 |
10.5-300-1W | 10.5 | 300 | 8.67 | 28.6 |
10.5-334-1W | 10.5 | 334 | 9.65 | 31.8 |
6.35-50-1W | 6.35 | 50 | 3.95 | 7.87 |
6.35-100-1W | 6.35 | 100 | 7.89 | 15.75 |
6.35-150-1W | 6.35 | 150 | 11.84 | 23.6 |
6.35-200-1W | 6.35 | 200 | 15.78 | 31.5 |
6.35-300-1W | 6.35 | 300 | 23.68 | 47.2 |
6.35-334-1W | 6.35 | 334 | 26.36 | 52.6 |
3.81-50-1W | 3.81 | 50 | 10.96 | 13.12 |
3.81-100-1W | 3.81 | 100 | 21.9 | 26.24 |
3.81-150-1W | 3.81 | 150 | 32.9 | 39.36 |
3.81-200-1W | 3.81 | 200 | 43.8 | 52.48 |
3.81-300-1W | 3.81 | 300 | 65.8 | 78.7 |
3.81-334-1W | 3.81 | 334 | 73.2 | 87.6 |
11-100-1W | 11 | 100 | 2.63 | 9.1 |
11-150-1W | 11 | 150 | 3.95 | 13.6 |
11-200-1W | 11 | 200 | 5.26 | 18.2 |
11-300-1W | 11 | 300 | 7.89 | 27.3 |
11-334-1W | 11 | 334 | 8.79 | 30.4 |
12-100-1W | 12 | 100 | 2.2 | 8.33 |
12-150-1W | 12 | 150 | 3.3 | 12.5 |
12-200-1W | 12 | 200 | 4.4 | 16.7 |
12-300-1W | 12 | 300 | 6.64 | 25 |
12-334-1W | 12 | 334 | 7.39 | 27.8 |
6.93-100-1W | 6.93 | 100 | 6.63 | 14.4 |
6.93-150-1W | 6.93 | 150 | 9.95 | 21.7 |
6.93-200-1W | 6.93 | 200 | 13.3 | 28.9 |
6.93-300-1W | 6.93 | 300 | 19.9 | 43.3 |
6.93-334-1W | 6.93 | 334 | 22.1 | 48.2 |
6.93-400-1W | 6.93 | 400 | 26.54 | 57.74 |
6.3-100-1W | 6.3 | 100 | 8 | 15.9 |
6.3-150-1W | 6.3 | 150 | 12 | 23.8 |
6.3-200-1W | 6.3 | 200 | 16 | 31.7 |
6.3-300-1W | 6.3 | 300 | ishirini na nne | 47.6 |
6.3-334-1W | 6.3 | 334 | 26.8 | 53 |
6.6-100-1W | 6.6 | 100 | 7.3 | 15.2 |
6.6-150-1W | 6.6 | 150 | 11 | 22.7 |
6.6-200-1W | 6.6 | 200 | 14.6 | 30.3 |
6.6-300-1W | 6.6 | 300 | ishirini na mbili | 45.5 |
6.6-334-1W | 6.6 | 334 | 24.4 | 50.6 |
3.81-100-1W | 3.81 | 100 | 21.9 | 26.24 |
3.81-150-1W | 3.81 | 150 | 32.9 | 39.36 |
3.81-200-1W | 3.81 | 200 | 43.8 | 52.48 |
3.81-300-1W | 3.81 | 300 | 65.8 | 78.7 |
3.81-334-1W | 3.81 | 334 | 73.2 | 87.6 |
6.35-100-1W | 6.35 | 100 | 7.89 | 15.75 |
6.35-150-1W | 6.35 | 150 | 11.84 | 23.6 |
6.35-200-1W | 6.35 | 200 | 15.78 | 31.5 |
6.35-300-1W | 6.35 | 300 | 23.68 | 47.2 |
6.35-334-1W | 6.35 | 334 | 26.36 | 52.6 |
11-100-1W | 11 | 100 | 2.63 | 5.25 |
11-150-1W | 11 | 150 | 3.95 | 7.87 |
11-200-1W | 11 | 200 | 5.26 | 10.5 |
11-300-1W | 11 | 300 | 7.9 | 15.75 |
11-100-1W | 11 | 100 | 2.63 | 5.25 |
11-150-1W | 11 | 150 | 3.95 | 7.87 |
11-200-1W | 11 | 200 | 5.26 | 10.5 |
11-300-1W | 11 | 300 | 7.9 | 15.75 |
12-100-1W | 12 | 100 | 2.2 | 4.8 |
12-150-1W | 12 | 150 | 3.3 | 7.2 |
12-200-1W | 12 | 200 | 4.4 | 9.6 |
12-300-1W | 12 | 300 | 6.64 | 14.45 |
12-100-1W | 12 | 100 | 2.2 | 4.8 |
12-150-1W | 12 | 150 | 3.2 | 7.2 |
12-200-1W | 12 | 200 | 4.4 | 9.6 |
12-300-1W | 12 | 300 | 6.64 | 14.45 |
11/√3-200-1W | 11/√3 | 200 | 15.78 | 31.5 |
11/√3-334-1W | 11/√3 | 334 | 26.36 | 52.6 |
12/√3-200-1W | 12/√3 | 200 | 13.3 | 28.9 |
12/√3-334-1W | 12/√3 | 334 | 22.1 | 48.2 |
12-200-1W | 12 | 200 | 4.4 | 16.7 |
12-334-1W | 12 | 334 | 7.39 | 27.8 |
10.5-200-1W | 10.5 | 200 | 5.8 | 19 |
10.5-334-1W | 10.5 | 334 | 9.65 | 31.8 |